Transformer Sizing Calculator

Enter your transformer’s kVA and voltages. You get the full load current, wire size, and largest fuse or breaker for both sides.

kVA
2Phase
V
V
5Wire material
6Electrical code
7Fuses or breakers on

Example values are filled in. Replace them with the numbers on your transformer’s nameplate.

Your results

Planning guide only. Always confirm sizes against the nameplate and your local code or inspector before you buy or install.
Good to know
  • Nameplate wins. Calculated current is a guide. Real transformers vary with impedance and design.
  • Inrush. Transformers draw 8–12× full load current for a moment on startup. Use time-delay fuses or inverse-time breakers. Ontario guidance says the device should carry about 12× full load current for 0.1 s and 25× for 0.01 s.
  • Wire size. Wire is sized at 125% of full load current (CEC Section 26), from copper or aluminum THWN-2 at 75°C, 30°C ambient. Long runs, hot areas or many wires in one conduit need larger wire.
  • Fuse or breaker size. The result is the largest size the code allows, not a recommendation. Canada (CEC Section 26, as used by ESA in Ontario): the usual setup is primary-only protection at up to 125% of primary current, with the next standard size up allowed. That primary fuse also protects secondary wire sized at 125% or more of secondary current. If the secondary has its own fuse (125% of secondary current), the primary may go up to 300%. USA (NEC 450.3(B)): primary 125% (167% or 300% for small currents) with primary-only protection, or 250% when the secondary is also protected. Rule numbers change between code editions (for example 26-254 and 26-256 in the 2018 CEC), so confirm yours with ESA.
  • Fuse and wire pairing (Canada). The CEC is national, but each province adopts its own edition and inspectors apply it differently. To suit the strictest, the calculator never leaves a fuse larger than the wire it protects. When rounding the fuse up would do that, it shows two ways to fix it: a smaller standard fuse on the same wire, or a larger wire.
  • Aluminum. Use AL/CU-rated lugs and anti-oxidant compound at every termination.
Full disclaimer

All full load amperage (FLA) values, wire gauge suggestions, and fuse/breaker sizing shown on this page are typical calculated figures for general planning purposes only. Values are derived from standard formulas and common NEC/CEC ampacity tables (THWN-2 copper and aluminum at 75°C) and do not account for individual transformer design variations, impedance ratings, efficiency losses, temperature rise class, winding configurations, conduit fill, ambient temperature derating, harmonic loading, voltage drop, or manufacturer-specific tolerances. Actual FLA and required conductor/protection sizes will differ from calculated values.

Always verify using the transformer nameplate. All conductor sizing, OCPD selection, fuse sizing, and electrical installations must comply with the applicable NEC, Canadian Electrical Code (CEC) Section 26, or standards enforced by the Authority Having Jurisdiction (AHJ). This reference does not constitute engineering advice. Always engage a licensed professional for final design, sizing, and installation decisions. The publisher assumes no liability for errors, omissions, or outcomes from use of this information.