Motor Sizing Calculator

Pick the motor’s horsepower, phase and voltage. You get the full load current, wire size, fuse or breaker, overload setting, starter size and disconnect.

1Phase
HP
3Voltage
4Wire material
5Electrical code
Have the motor nameplate? Add it for a better overload setting (optional)
A
Service factor / temperature rise

Your results

Planning guide only. Always confirm sizes against the motor nameplate, the starter and breaker manufacturer’s data, and your local code or inspector before you buy or install.
How these are figured
  • Full load current (FLC): from the code motor tables (NEC 430.250 / 430.248). In Canada, the nameplate current is used when you enter it; otherwise the table value is used.
  • Wire: at least 125% of FLC, from the 75°C single-conductor ampacity table (NEC 310.16 / CEC Table 2). Applies to one continuous-duty motor.
  • Short-circuit protection: the largest fuse or breaker allowed, as a percent of FLC: inverse-time breaker 250%, time-delay fuse 175%, non-time-delay fuse 300%, instantaneous-trip 800% (NEC 430.52 / CEC Rule 28-200, Table 29). The USA mode rounds up to the next standard size; the Canada mode rounds down to stay at or below the limit. If the motor will not start, the codes allow a larger size; ask your inspector or the manufacturer.
  • Overload: from the nameplate amps: 125% for motors with a service factor of 1.15 or more or a temperature rise of 40°C or less; 115% for all other motors (NEC 430.32(A)(1) / CEC Rule 28-306).
  • Disconnect: rated at least 115% of FLC (NEC 430.110). Confirm the Canadian requirement with your inspector.
  • Starter: smallest NEMA size whose horsepower rating covers the motor at its voltage.
  • Variable frequency drives: size wire from the drive’s input current rating (NEC 430.122), not this table.
Disclaimer

All full load current values, wire sizes, protection sizes and starter sizes shown on this page are typical figures for general planning purposes only. They do not account for ambient temperature or conduit fill derating, voltage drop, motor design letter, duty cycle, altitude, harmonics or manufacturer variations.

Always verify with the motor nameplate and the equipment manufacturer’s data. Every installation must comply with the NEC, the Canadian Electrical Code (CEC) Section 28, the Ontario Electrical Safety Code or the rules of the Authority Having Jurisdiction. This is not engineering advice; engage a licensed professional for final design. Airwill Electrical Supply Inc. assumes no liability for errors, omissions or results of using this tool.