Motor Sizing Calculator
Pick the motor’s horsepower, phase and voltage. You get the full load current, wire size, fuse or breaker, overload setting, starter size and disconnect.
Have the motor nameplate? Add it for a better overload setting (optional)
Your results
Tap a row to send that motor to the calculator. Values are NEC Tables 430.250 and 430.248 (typical induction motors). Use the nameplate if the motor is unusual (high-speed, low-speed, multi-speed).
NEMA ICS 2 ratings for general-purpose full-voltage starters. IEC contactors are sized differently; check the maker’s selection chart. Plugging, jogging or reversing duty may need a larger size.
How these are figured
- Full load current (FLC): from the code motor tables (NEC 430.250 / 430.248). In Canada, the nameplate current is used when you enter it; otherwise the table value is used.
- Wire: at least 125% of FLC, from the 75°C single-conductor ampacity table (NEC 310.16 / CEC Table 2). Applies to one continuous-duty motor.
- Short-circuit protection: the largest fuse or breaker allowed, as a percent of FLC: inverse-time breaker 250%, time-delay fuse 175%, non-time-delay fuse 300%, instantaneous-trip 800% (NEC 430.52 / CEC Rule 28-200, Table 29). The USA mode rounds up to the next standard size; the Canada mode rounds down to stay at or below the limit. If the motor will not start, the codes allow a larger size; ask your inspector or the manufacturer.
- Overload: from the nameplate amps: 125% for motors with a service factor of 1.15 or more or a temperature rise of 40°C or less; 115% for all other motors (NEC 430.32(A)(1) / CEC Rule 28-306).
- Disconnect: rated at least 115% of FLC (NEC 430.110). Confirm the Canadian requirement with your inspector.
- Starter: smallest NEMA size whose horsepower rating covers the motor at its voltage.
- Variable frequency drives: size wire from the drive’s input current rating (NEC 430.122), not this table.
Disclaimer
All full load current values, wire sizes, protection sizes and starter sizes shown on this page are typical figures for general planning purposes only. They do not account for ambient temperature or conduit fill derating, voltage drop, motor design letter, duty cycle, altitude, harmonics or manufacturer variations.
Always verify with the motor nameplate and the equipment manufacturer’s data. Every installation must comply with the NEC, the Canadian Electrical Code (CEC) Section 28, the Ontario Electrical Safety Code or the rules of the Authority Having Jurisdiction. This is not engineering advice; engage a licensed professional for final design. Airwill Electrical Supply Inc. assumes no liability for errors, omissions or results of using this tool.