(905) 458 7027

Motor cable and Overload Sizing

Motor Sizing Reference & Calculator | Airwill
Airwill Support · Motor Tools

Motor Sizing Reference & Calculator

Full load current (FLC) lookup, wire gauge, contactor sizing, overload relay, fuse and breaker selection for single-phase and three-phase AC motors. Based on NEC Article 430 and CEC Section 28. Use as a starting point — always confirm against the motor nameplate and applicable code.

FLC vs FLA

Use NEC table FLC for conductor and breaker sizing. Use nameplate FLA for overload relay setting. They are different — mixing them up causes improper protection.

125% conductor rule

Branch circuit conductors must be sized at ?125% of table FLC per NEC 430.22. This accounts for the heat generated by continuous motor operation.

Contactor sizing

NEMA contactors are sized by HP and voltage. The contactor handles inrush; the overload relay protects the motor. Both must be correctly selected.

Overload relay

Set at 115–125% of nameplate FLA (NEC 430.32). A thermal overload set too high is useless — it will let the motor burn before tripping.

Inrush / starting

Motors draw 6–8× FLC on start. Branch circuit breakers and fuses must handle this. Dual-element fuses ?175% FLC; inverse-time breakers ?250% FLC.

Critical: FLC (Table) vs FLA (Nameplate) — Know the Difference

Table FLC (NEC 430.248 / 430.250): Used for sizing branch circuit conductors (NEC 430.22), branch circuit protection devices (NEC 430.52), and disconnect switches (NEC 430.110). This calculator uses table FLC.

Nameplate FLA: Used for sizing overload relay protection only (NEC 430.32). The overload relay setting must be based on the actual motor nameplate current, NOT the table value. Enter your nameplate FLA in the calculator below to get the correct overload relay range.

Disclaimer — Important: Read Before Use

All FLC values, wire gauge, contactor, overload relay, fuse, and breaker suggestions on this page are typical calculated figures for general planning purposes only. FLC values are from NEC Tables 430.248 and 430.250 for standard squirrel-cage induction motors at normal speeds and torques. These values do not apply to low-speed motors (<1200 RPM), high-torque motors, multispeed motors, wound-rotor motors, synchronous motors, or motors operated with VFDs — which require nameplate-based sizing. Wire gauge is based on NEC Table 310.16 (THWN-2, 75°C, single conductor in conduit at 30°C ambient) without conduit fill derating. Contactor and overload sizing is based on NEMA ICS 2 standard full-voltage-start, AC-3 duty ratings and may differ for jogging, plugging, reversing, or high-cycle applications. Always use the motor nameplate FLA for overload relay settings per NEC 430.32.

All electrical installations must comply with the applicable NEC, Canadian Electrical Code (CEC Section 28), and standards enforced by the Authority Having Jurisdiction (AHJ). This reference does not constitute engineering advice. Always engage a licensed professional for final design, sizing, and installation decisions. The publisher assumes no liability for errors, omissions, or outcomes resulting from use of this information.

NEC 430.22: Branch circuit conductors ? 125% of table FLC. Next standard ampacity size up.
NEC 430.52: Max branch circuit breaker = 250% FLC. Max dual-element fuse = 175% FLC.
NEC 430.32: Overload relay set at 115–125% of NAMEPLATE FLA, not table FLC.
CEC Section 28: Canadian rules differ slightly. Confirm with your province's adopted CEC edition and AHJ.
Inrush: Motors draw 6–8× FLC on start. NEMA contactors are rated for this — IEC contactors require careful AC-3 duty verification.

Enter motor parameters

Select HP, voltage, and phase to calculate — enter nameplate FLA for overload relay sizing.

Why use table FLC, not nameplate FLA?

NEC 430.6(A)(1) requires table values for conductor and protection sizing — not nameplate data. This standardises sizing across all motors of the same HP/voltage regardless of efficiency differences between manufacturers.

Overload relay — service factor

SF ? 1.15: set overload at ?115% nameplate FLA. SF < 1.15 or 40°C rise: set at ?125%. Trip class 10 is standard; use class 20 or 30 for high-inertia loads like fans and compressors.

NEMA contactor sizing

Select by HP and voltage from NEMA ICS 2 tables. Contactor handles inrush and breaking duty. For jogging, plugging, or reversing, derate to next size up — these duties are much harder on contacts.

VFD applications

Variable frequency drives change motor current profiles significantly. Conductor sizing and overload protection with VFDs follow NEC 430.122 — contact the VFD manufacturer for specific sizing guidance.

Branch circuit protection

Dual-element (time-delay) fuses: max 175% FLC. Inverse-time breakers: max 250% FLC. If the motor won't start, these limits may be increased up to 225% (fuse) or 400% (breaker) per NEC 430.52 Exception.

Disconnect sizing

Motor disconnect must be rated ?115% of motor FLC (NEC 430.110). For combination starters, the disconnect is built in. Standalone disconnects are typically sized 1–2 current ratings above the motor FLC.

Voltages:

Source: NEC Table 430.250. Values for squirrel-cage induction motors at normal speeds and torques. Use table FLC (not nameplate FLA) for conductor sizing per NEC 430.22 and branch circuit protection per NEC 430.52.

Voltages:

Source: NEC Table 430.248. Values for single-phase motors at normal speeds and torques. 115V and 230V are the most common single-phase motor voltages in North America.

NEMA starter sizes are selected by motor HP and voltage for full-voltage (across-the-line) starting. Confirm overload relay is set to 115–125% of nameplate FLA per NEC 430.32, regardless of starter size chosen.

NEMA SizeMax continuous AMax HP @ 200VMax HP @ 230VMax HP @ 460/480VMax HP @ 575/600VTypical application
009 A1.5 HP1.5 HP2 HP2 HPSmall fans, fractional HP, light conveyor
018 A3 HP3 HP5 HP5 HPSmall pumps, HVAC, general purpose
127 A7.5 HP7.5 HP10 HP10 HPSmall industrial motors, conveyors, compressors
245 A10 HP15 HP25 HP25 HPMedium pumps/fans, material handling
390 A25 HP35 HP50 HP50 HPHeavier conveyors, process pumps, compressors
4135 A40 HP50 HP100 HP100 HPLarge process loads, high-inertia equipment
5270 A75 HP100 HP200 HP200 HPLarge industrial motors, MCCs
6540 A150 HP200 HP400 HP400 HPHeavy industrial, large process equipment
7810 A300 HP600 HP600 HPVery large industrial applications
81215 A450 HP900 HP900 HPLarge MCC / power distribution
92250 A800 HP1600 HP1600 HPUtility-scale industrial motors

Source: NEMA ICS 2, full-voltage start, AC-3 duty. For jogging, plugging, reversing, or high-cycle duty, select the next size up. IEC contactors are sized differently using AC-3/AC-4 utilization categories — consult manufacturer selection guides.

FLC vs FLA — the critical distinction

FLC from NEC tables is used for conductor and breaker sizing (430.22, 430.52). Nameplate FLA is used for overload relay setting (430.32). Using the wrong value for each leads to either undersized protection or nuisance tripping.

Branch circuit conductor (NEC 430.22)

Single motor: conductors must have ampacity ? 125% of table FLC. For multiple motors on one feeder, see NEC 430.24 — largest motor at 125%, all others at 100%.

Branch circuit protection (NEC 430.52)

Dual-element time-delay fuse: max 175% FLC. Inverse-time breaker: max 250% FLC. If motor won't start, can increase to 225% (fuse) or 400% (breaker) per NEC 430.52 Exception No. 1.

Overload relay — NEC 430.32

Set at ?115% nameplate FLA for motors with SF ? 1.15 or 40°C temperature rise marked. Set at ?125% for all other motors. Trip Class 10 is standard; Class 20/30 for high-inertia loads.

Contactor selection — NEMA

Select NEMA size from HP and voltage table. For jogging, plugging, or reversing duty, derate one size up. Verify SCCR (short circuit current rating) matches available fault current at the installation point.

IEC vs NEMA contactors

NEMA: rugged, oversized for the duty, easy selection by HP. IEC: compact, precisely sized by AC-3/AC-4 utilization category. IEC requires more careful duty-cycle matching but is smaller and lower cost.

Disconnect sizing (NEC 430.110)

Motor disconnect must be rated ?115% of motor FLC. Horsepower-rated disconnects must be rated for the motor HP and voltage. Fusible disconnects provide combined disconnect and short-circuit protection.

Conduit and conduit fill

More than 3 current-carrying conductors requires ampacity derating per NEC 310.15(C). For motor circuits with ground wire, ensure conduit is sized for all conductors including the EGC per NEC 430.23.

VFD motor circuits (NEC 430.122)

VFD branch circuit conductors must be sized at ?125% of VFD input FLC rating. Motor lead wire from VFD to motor should be VFD-rated cable. Overload protection is typically built into the VFD.

Motor starting methods

Across-the-line: 6–8× FLC inrush. Star-delta: reduces inrush to ~33%. Soft starter: adjustable ramp, reduces inrush to ~2–4×. VFD: lowest inrush, best control. Starting method affects contactor and cable sizing.

CEC Section 28 (Canada)

Canadian motor circuit rules are in CEC Section 28. Branch circuit protection rules differ slightly from NEC 430.52. Confirm with the CEC edition adopted by your province and the local AHJ.

Motor circuit application guide

Pump/fan loads: standard duty, Class 10 overload. Compressors: high inertia, Class 20. Conveyor/crusher: high torque, may need Class 30. Jogging/reversing: derate contactor and use appropriate relay.

Low-speed & special motors

Motors <1200 RPM, high-torque motors, wound-rotor, synchronous, and multispeed motors: NEC 430.6(A)(2) requires using nameplate FLA (not table FLC) for conductor and protection sizing.

Always consult the AHJ

Local amendments to NEC or CEC may impose additional requirements. The Authority Having Jurisdiction has final say on code interpretation. Consult a licensed engineer or inspector when in doubt.